For a good cable you will see results similar to those on the following page.
11kv cable insulation resistance test values.
I have found in the past that if you contact the manufacturer of the cable they will advise you on the appropriate test voltages time period also speak to a recognised good mv cable test engineer s.
You have a single conductor 500 kcmil 15kv cable.
Curve b shows same values corrected to 20 c see page 22 giving a definite downward.
If during periodical testing insulation resistance of cable is found between 5 and 1 mω km at buried temperature the subject cable should be programmed for replacement.
Curve a shows test values as measured.
5kv insulation resistance test on cable oversheath for 33kv xlpe cables in accordance with section 10 2 2.
3 shows a typical scale which reads increasing resistance values from left up to infinity or a resistance too high to be measured.
Ansi neta mts 2015 table 100 11 insulation resistance test values rotating machinery for one minute at 40 c.
5kv insulation resistance tester 10 kv for 12 7 22 and 19 33 kv cables.
If during periodical testing insulation resistance of cable is found between 5 and 1 mω km at buried temperature the subject cable should be programmed for replacement.
For pvc sheathed cables the acceptance value is 1 m.
The resistance values will increase over time due to capacitive and insulation charging.
Hands down without a doubt one of the most universally searched topics on ec m s website from a historical perspective is insulation resistance testing as a result some of our most popular evergreen articles like understanding insulation resistance testing continue to top the charts when it comes to most popular content.
You perform this insulation resistance test on the cable and record the data on a copy of the attached form.
Figure 4 typical record of insulation resistance of a mill motor.
And barricade exposed ends of cable during insulation test.
A rated line to line voltage for three phase ac machines line to ground voltage for single phase machines and rated direct voltage for dc machines or field windings.
Since 80 of electrical maintenance and testing.
The values i have used for 6 35 11kv cu xlpe swa pvc cables in practice has been.
Electrical insulation testing of hv equipment.
All other 11kv cable.
Test values table 8.
Values based on ieee std 43 2013.
What is the permissible leakage current value for a 11kv cable if there any formula for calculating leakage current cable rated voltage 8 7 to 15 kv 2070 meter length ac hi pot test kit applied volt.
Refer to swp sp0506 substation primary plant and secondary.
5kv megger dc insulation test phase to earth for 2 3 mins.
5kv insulation resistance test megger.
If insulation resistance of the cable is found between 1000 and 100 kω km at buried temperature the subject cable should be replaced urgently within a year.
It may be prudent in certain circumstances to pressure test the cable section prior to.